Igloo Cellulose insulation France

Cellulose Igloo France penguins

What regulations apply to thermal insulation work?

Share this article

When renovating, insulation work is governed by thermal regulations. These regulations set minimum thermal performance requirements for insulation work, depending on the walls and geographical area. However, some financial assistance for insulation work requires thresholds higher than those set by these regulations. Finally, the regulations also make thermal insulation work mandatory for certain types of major renovation work. We have therefore compiled this information in our comprehensive guide, which tells you everything you need to know about the regulations governing thermal insulation work during renovation.

When carrying out thermal insulation work, the thermal regulations defined in the decree of May 3, 2007, amended by the decree of March 22, 2017, must be complied with. These regulations apply to existing buildings and specify the minimum thermal characteristics and energy performance requirements that must be met. The regulatory requirements described above are the minimum performance levels required by the regulations for the thermal renovation of housing (particularly during insulation work).

However, higher performance criteria are possible and sometimes even required in order to obtain certain financial assistance: these elements are also detailed in this comprehensive guide to regulations for thermal insulation work.

Carrying out energy renovation workimproves a home'sthermal insulation, reducing the cold wall effect and maintaining a stable temperature inside the building. Good thermal insulation reduces energy loss and therefore the need for heating and/or air conditioning. Thermal renovation work therefore leads to energy savings.

1.1.1 What work for which walls?

Regulations governing thermal renovation apply as soon as you begin work to improve insulation or renovate the exterior of your home. They apply to all types of roofs, as well as terracotta or concrete floors, and walls made of industrial bricks, industrial concrete blocks, poured concrete, or metal cladding. Other types of walls are not yet subject to these requirements. In all cases, it is mandatory to maintain existing air inlets in the walls or to install them if the main room is not ventilated.


The regulations cover work related to interior or exterior insulation, whether for minor repairs or major renovations.
Exemptions are provided if the work alters the appearance of the building in a manner that is incompatible with the requirements for heritage sites, the surroundings of historic monuments, listed or classified sites, or urban planning regulations. The work is also exempt from the regulations if it is carried out in response to special circumstances such as natural disasters or acts of vandalism.

1.1.2 Thermal regulation requirements for wall insulation work

Thermal regulations set minimum performance levels to be achieved in terms of thermal resistance (R), measured in m².K/W. These levels vary according to climate zones and the type of walls to be insulated.

Minimum thermal resistance values R of the insulated wall
, valid from January 1, 2023 (m2.K/W):

Wall typeClimate zone H1Climate zone H2
s (H3 > 800m altitude)
Zone climatique H3
(< 800m d’altitude)
Exterior wall, roof slope >60°3,23,22,2
Wall in contact with an unheated space2,52,52,5
Low floor opening onto the outside or onto an unheated room3*3*3*
Attic floors5,25,25,2
Toiture de pente <60°5.24.54
Flat roof4.5***4.3***4***
Table 1: Minimum thermal resistance values R for insulated walls valid from January 1, 2023 (m2.K/W)

*R = 2.1 possible to adapt the thickness of insulation required to the available headroom if this is limited by another regulatory requirement.
** R = 4 possible if the reduction in living space is greater than 5% due to the thickness of the insulation.
*** R = 3 possible in the following cases: the thickness of the insulation requires a change in the door and window frames, or a raising of the guardrails or technical equipment, or the thickness of the insulation no longer allows compliance with the minimum heights for rainwater drainage and flashings, or the thickness of the insulation and the type of insulation used exceeds the permissible limits of the structure.

1.1.3 Minimum thermal resistance for wall insulation

To comply with regulations, the insulation installed must enable the wall + insulation assembly to achieve at least the required thermal resistance value. The wall alone has a certain thermal resistance, but it is generally low compared to that of the insulation. If insulation is already present before renovation work begins and its thermal resistance is unknown, it can be calculated as follows:

  • For polyurethane foam and extruded polystyrene, multiply the thickness of the insulation (in cm) by 0.33.
  • For bio-based insulation materials, use the inverse of the thermal conductivity values in W/(m.K) indicated in Appendix IX of the Decree of October 26, 2010 (thermal characteristics and energy performance requirements for new buildings and new parts of buildings).
  • For other types of insulation, multiply the thickness of the insulation (in cm) by 0.25.

Insulation interrupted by a frame is less effective than continuous insulation. This reduction in performance must be taken into account in calculations: if the frame is made of wood, consider 80% of the R-value indicated or calculated; if it is made of metal, consider only 50%.

In the interests of efficiency and cost reduction, regulations require thermal insulation work to be carried out as part of certain types of work (Decree No. 2016-711 of May 30, 2016). This is the case, for example, for facade renovation, roof repair, or the conversion of premises to make them habitable. Insulation work is therefore included in major building renovations

The regulations specify the cases in which thermal insulation work is mandatory when carrying out major works. The constraints for occupants and the costs inherent in this type of operation are then concentrated in a single intervention, which allows for savings and streamlines the preparation of administrative files, the installation of the site, its organization, waste management, etc.
Certain types of work are particularly well suited to the joint installation of high-performance thermal insulation, as once completed, these elements will not be renovated again for many years.

This is particularly the case for:
– façade renovations;
– roof repairs;
– conversions to increase living space.

Thus, the regulations imposed by the decree of May 30, 2016, in application of the Energy Transition for Green Growth Act, require that work to improve the thermal performance of a building (particularly insulation) be carried out in conjunction with major renovation work, since January 1, 2017.

a. Facade renovation

For certain buildings (constructed from industrial materials), in the event of major facade renovation, regulations require that thermal insulation be installed at the same time. Logically, this insulation is installed from the outside at the same time as the renovation work, but the owner may, if they wish, comply with the requirement by installing insulation from the inside. Please note that certain conditions must be met in order for the insulation to be suitable for the facade renovation and for it to be cost-effective.

  • Buildings concerned: individual and collective residential buildings and tertiary buildings (offices, educational establishments, hotels, shops) located in mainland France.
  • Facades concerned: facades consisting of more than 50% terracotta, concrete, cement, or metal surfaces. The regulations therefore apply to facades made of industrial (non-handcrafted) bricks, poured concrete, cinder blocks, single-wall bricks, or metal cladding (walls mainly composed of industrial materials with hygrothermal properties that differ from those of traditional buildings).
  • Renovations concerned: renovations affecting more than 50% of the facade and consisting of either removing and redoing the existing coating, or adding or replacing cladding on the facade.
  • Preliminary steps: Conducting an energy audit is recommended and sometimes mandatory for residential buildings before undertaking thermal renovation. A preliminary declaration must be submitted to the local authorities for all buildings planning to install exterior insulation.
Performance requirement:

Thermal regulations applicable to existing buildings require that walls (wall + insulation) in contact with the outside must, after renovation, have a minimum thermal performance R, the values of which since January 1, 2023 are (inm2.K/W):

Opaque wall typeClimate zones H1, H2, H3 (> 800 m altitude)Zone climatique H3
(< 800m d’altitude)
Exterior wall3,22,2
Wall in contact with an unheated space2,52,5
Table 2: Minimum thermal performance values R for walls in contact with the outside as of January 1, 2023 (inm2.K/W).

b. Roof repair

When carrying out major roof repairs, it may be mandatory to install thermal insulation at the same time. This insulation can be installed in the attic, which is particularly recommended when renovating old buildings. However, the regulations provide for exemptions to this obligation in the event of technical, legal, architectural, or economic constraints.

  • Buildings concerned: individual and collective residential buildings and tertiary buildings (offices, educational establishments, hotels, shops) located in mainland France.
  • Renovations concerned: insulation work is mandatory if the roof is being renovated (removal of the existing roof and replacement with a new roof) or if a roof overlay is being installed; if the renovation covers more than 50% of the roof (excluding openings).
Performance requirement:

After completion of the work, the roof (wall + insulation) must have a minimum thermal performance with the following R values (inm2.K/W):

Opaque wall typeClimate zones H1, H2, H3 (> 800 m altitude)Zone climatique H3
(< 800m d’altitude)
Attic floor5,25,2
Converted attic space, roof pitch ≤ 60°H1 = 5.2*
H2 = 4.5*
4
Roof pitch > 60°3,22,2
Flat roofH1 = 4.5**
H2 = 4.3**
4**
Table 3: Minimum thermal performance values R for roofing (inm2.K/W).

* R = 4 possible if the reduction in living space is greater than 5% due to the thickness of the insulation.
** R = 3 possible in the following cases: the thickness of the insulation requires a change in the door and window frames, or a raising of the guardrails or technical equipment, or the thickness of the insulation no longer allows compliance with the minimum heights for rainwater drainage and flashings, or the thickness of the insulation and the type of insulation used exceeds the permissible limits of the structure.

c. Increase in living space

When renovating a room to make it habitable, there may be an obligation to install thermal insulation at the same time. The regulations provide for an exemption from this obligation in the event of technical constraints.

  • Buildings concerned: individual and multi-unit residential buildings located in mainland France.
  • Rooms and walls concerned: the converted room may be an attic, laundry room, garage, etc. It must not be underground or semi-underground, and its floor area must be ≥5m² once the work has been completed. The walls affected by thermal regulations are opaque walls: exterior walls (only industrial brick facades, industrial concrete blocks, formwork concrete, and metal cladding of converted rooms are affected), roofs (sloped roofs or flat roofs), and low floors if they open onto the exterior or an unheated room.
Performance requirement

The opaque walls of the converted space (wall + insulation) must have a minimum thermal performance R after work, with the following values (inm2.K/W):

Opaque wall typeClimate zones H1, H2, H3
(> 800 m altitude)
Zone climatique H3
(< 800m d’altitude)
Wall facing the outside3,22,2
Wall in contact with an unheated space2,52,5
Low floor opening onto the outside or onto an unheated room3*2,1
Attic floor5,25,2
Roof slope ≤ 60°H1 = 5.2**
H2 = 4.5**
4
Roof slope > 60°3,22,2
Flat roofH1 = 4.5***
H2 = 4.3***
4***
Table 4: Minimum thermal performance values R for opaque walls (inm2.K/W).

*R = 2.1 possible to adapt the thickness of insulation required to the available headroom if this is limited by another regulatory requirement.
** R = 4 possible if the reduction in living space is greater than 5% due to the thickness of the insulation.
*** R = 3 possible in the following cases: the thickness of the insulation requires a change in the door and window frames, or a raising of the guardrails or technical equipment, or the thickness of the insulation no longer allows compliance with the minimum heights for rainwater drainage and flashings, or the thickness of the insulation and the type of insulation used exceeds the permissible limits of the structure.

However, the regulations provide for exceptions.Thermal insulation is not mandatory when the work proves impossible or disproportionate. It is still recommended, however, as it offers many advantages: lower energy bills, increased property value, and improved comfort. Please note that in some cases, the authorities may request proof during an unannounced inspection.

If the work is disproportionate, what should be done to verify or certify this?

a. In the event of technical constraints: if the work poses a risk of damage to the building

This exemption applies to insulation work carried out in conjunction with façade renovation, roof repair, or the conversion of a room to make it habitable. In the latter case, this is the only possible exemption from the obligation to carry out work.
It is recommended that you use a professional who is competent in the areas of work to be carried out (architect, qualified design office, contractor, and craftsman). They must check whether the thermal insulation work is likely to cause serious damage to the building. If so, the obligation to carry out the work does not apply.
The professional must provide the owner with a reasoned note as proof.

b. In the event of legal constraints: in particular if the project is not compatible with urban planning regulations

In the event of insulation work being carried out in conjunction with renovation or roof repair work, the project manager or building owner must check that the project complies with local planning regulations. They must also check that the architect who designed the building (or their legal representative) does not object to the project on intellectual property grounds.
If the insulation work does not comply with the town planning regulations applicable in the municipality (Local Urban Development Plan, etc.), property law or the rules and regulations applicable to remarkable heritage sites, areas surrounding historic monuments and listed or classified sites, the obligation to carry out the work does not apply.
No supporting documents are required to prove this legal impossibility to carry out the work.

c. In the event of architectural constraints: if the work alters the architectural quality of the building

In the case of insulation combined with renovation or roof repair, an architect must verify whether exterior insulation work alters the appearance of the building and degrades its architectural quality or that of the neighborhood/district. If this is the case, the obligation to carry out the work does not apply.
The architect must provide the owner with a reasoned note as justification.

d. In the event of economic constraints: if the project is not profitable

The project is considered unprofitable if its return on investment period is strictly greater than 10 years. The calculation of this payback period is not necessary if, given the characteristics of the building, it is clear that this payback period is greater than 10 years.
If the project is not profitable, it is necessary to produce supporting documentation:
– by a professional if the calculation of the payback period is necessary;
– by the project owner if the calculation is not mandatory.

Calculating the return on investment is necessary:

In the case of insulation combined with roof renovation or repair, to calculate the payback period, it is recommended to consult a specialist, who may be:
– an RGE-qualified thermal engineering firm or an RGE-qualified economist;
– an RGE-qualified energy auditor;
– an architect;
– an I.cert-certified energy renovation expert;
– an EPC diagnostician with special mention;
– an RGE* qualified or certified company in global renovation;
– an RGE Pro qualified company in energy performance or Eco Artisan.

This professional can calculate the return on investment for the work using the method described below. If the work is not sufficiently profitable, the obligation to carry out the work does not apply. For renovations, the calculation must be carried out facade by facade: the return on investment for insulating a gable may be less than 10 years, while for the main facade it may be more than 10 years.

The professional must provide supporting documentation: they draw up a note to justify the calculation of the return on investment.

e. Cases where calculating the return on investment is unnecessary

In some cases, the calculation is unnecessary, as the payback period is then deemed to be greater than 10 years.

In the case of façade renovation:
– building constructed after 2001;
– façade insulated after 2008;
– facade already insulated to achieve a thermal resistance greater than or equal to 2.3m2.K/W*;
– building that has already undergone an energy audit (less than 10 years ago) demonstrating that insulation was not appropriate (technical, legal, architectural, or economic constraints described above);
– presence of balconies less than 1 m deep;
– insulation work requiring the identical reconstruction of existing moldings;
– insulation work requiring asbestos removal.

* For example, with 8 cm of mineral wool, 9 cm of polystyrene, 10 cm of wood fiber insulation, or 10 cm of hemp wool.

In the case of roof renovation:
– building constructed after 2001;
– roof or upper floor of the top inhabited level insulated after 2008;
– roof or upper floor of the top inhabited level already insulated to achieve a thermal resistance greater than or equal to 2.5m2.K/W **;
– building that has already undergone an energy audit (less than 10 years ago) which showed that insulation was not appropriate (technical, legal, architectural or economic constraints described above);
– insulation work requiring asbestos removal.

** For example, with 10 cm of mineral wool or polystyrene, 12 cm of wood fiber insulation, or 12 cm of cellulose insulation .

Situation making insulation mandatorySituation that removes the obligation to isolate
BUILDING AND CONSTRUCTION CHARACTERISTICS
Building typeshops, educational facilities, hotels, offices, housing (collective or individual) located in mainland Franceother cases
WORK AREA
Facade renovationmore than 50% (per facade, excluding openings)less than 50%
Roof repairmore than 50% of the roofless than 50% of the roof
Room layoutfloor space ≥ 5 after renovationfloor area ≤ 5 after renovation
NATURE OF THE WORK
Facade renovationremoval and refurbishment of existing plaster or addition of claddingcleaning, repair, and painting
Roof repairrepair or installation of a roof overlayother work (demolding, waterproofing, painting, etc.)
Room layoutwork to make the room habitableother work
NATURE OF THE WALLS
Facade renovation
Room layout
facades made mainly of terracotta, concrete, cement, or metal.other cases (stones, raw earth, cob, etc.)
LEGAL CONSTRAINT
Facade renovation
Roof repair
project with insulation compliant with urban planning documentsinsulation project not compliant with urban planning documents
TECHNICAL CONSTRAINT
Facade renovation
Roof repair
Room renovation
no risk of diseasejustified risk of disease
ARCHITECTURAL CONSTRAINT
Facade renovation
Roof repair
no risk of damage to the architecturerisk of architectural deterioration justified
ECONOMIC CONSTRAINT
Facade renovation
Roof repair
return on investment period ≤ 10 yearsreturn on investment period > 10 years (justified by calculation or calculation unnecessary)
ECONOMIC CONSTRAINT: CHARACTERISTICS THAT MAKE CALCULATING THE PAYBACK PERIOD UNNECESSARY
Year of constructionbefore 2001after 2001
Year of insulationbefore 2008after 2008
EXISTING INSULATION
Facade renovationR < 2,3 m2.K/W*R ≥ 2.3m²·K/W**
Roof repairR < 2,5 m2.K/WR ≥ 2.5m²·K/W
Energy auditno audit report showing that the insulation is unsuitableexistence of an audit report showing that the insulation is not suitable
TECHNICAL CONSTRAINT
Facade renovationbalconies with a depth ≥ 1 m no asbestos removal, no identical reconstruction of moldingsbalcons d’une profondeur < 1m pas de désamiantage indispensable, pas de nécessité de reconstituer des modénatures à l’identique
Table 5: Summary of cases where regulations make thermal insulation work mandatory or not

*R < 2 m2.K/W en zone climatique H3
** R ≥ 2 m2.K/W en zone climatique H3

Starting in 2025, homes classified as F and G will be prohibited from being rented, encouraging major thermal renovations to achieve higher energy ratings.

The DPE rental ban applies to homes classified as F and G on the Energy Performance Certificate (EPC) scale, which assesses a building's energy and climate performance. This assessment, which is crucial to European energy policy, aims to reduce energy consumption and greenhouse gas emissions.

What are the energy efficiency criteria that will come into effect successively from January 1, 2023, then in 2025, 2028, and 2034?

The landlord must provide the tenant with decent housing. For housing to be considered "decent," the law stipulates that it must meet increasingly stringent minimum energy performance standards.

In mainland France, to be classified as "decent," a dwelling must:

  • as of January 1, 2023, have energy consumption (heating, lighting, hot water, ventilation, cooling, etc.), expressed in final energy, of less than 450 kWhFE/m²/year. This consumption is estimated in the EPC (note that this is final energy consumption and not primary energy consumption);
  • as of January 1, 2025, have at least an F rating on the Energy Performance Certificate (EPC);
  • as of January 1, 2028, have at least an E rating on the Energy Performance Certificate (EPC);
  • as of January 1, 2034, have at least a D rating on the Energy Performance Certificate.

These deadlines are summarized in the following table:

Due dateJanuary 1, 2023January 1, 2025January 1, 2028January 1, 2034
Minimum energy performance criterion or levelConsommation en énergie finale < 450 kWhEF/m²/anEnergy efficiency class FEnergy efficiency class EEnergy efficiency class D
Reference textsArticle 17, Law No. 2019-1147 of November 8,2019Article 6, Law No. 89-462 of July 6, 1989(version in force as of January1, 2023)Decree No. 2021-19 of January 11, 2021  Article 160, Law No. 2021-1104 of August 22,2021Article 6, Law No. 89-462 of July 6, 1989 (version in force on January1, 2025)Decree No. 2002-120 of January 30, 2002("decency" decree)
ApplicationApplication to new leases and renewals or tacit renewals of leases
Table 6: Minimum energy performance criteria for housing eligible for rental according to deadlines

Are you a homeowner or tenant? Find all the information you need at the Ministry of Ecological Transition and Territorial Cohesion.

There are several financial assistance programs to encourage energy-efficient building renovations: MaPrimeRénov’, energy saving certificates (CEE), zero-interest eco-loans, and local assistance programs. These programs can cover or contribute to the financing of comprehensive renovations or specific measures, such as thermal insulation upgrades. However, some assistance requires minimum performance levels that exceed the thresholds set by thermal regulations applicable to building renovations.

The MaPrimeRénov’ scheme finances the installation of a carbon-free heating or domestic hot water system. In addition, other work can be carried out: thermal insulation, energy audit, removal of an oil tank, dual-flow ventilation.

More details on the France Rénov’ website .

The MaPrimeRénov’ Parcours accompagné scheme aims to encourage households to undertake ambitious renovations by financing a significant portion of the work. It is available regardless of the energy rating of the home and regardless of household income.
To be eligible for the MaPrimeRénov’ Parcours accompagné scheme, the renovation project must result in a gain of at least two energy classes on the home's energy performance diagnosis. Two insulation measures must also be included in the renovation program.

More details on the France Rénov’ website .

The MaPrimeRénov’ Copropriété scheme is reserved for work carried out on the common areas of condominiums and on private areas declared to be of collective interest. This work is voted on at condominium general meetings.

More details on the France Rénov’ website .

Loc’Avantages is a tax scheme that allows landlords to benefit from a tax reduction provided they rent their property at a capped rent to tenants on low incomes.
Loc’Avantages entitles landlords to subsidies for renovation work on the property.

More details on the France Rénov’ website .

The Energy Saving Certificates (ESC) scheme requires energy suppliers to promote effective energy saving measures to consumers. This is a government-regulated obligation, with heavy financial penalties imposed on those who fail to comply.

More information on Energy Saving Certificates.

The VAT rate applied to renovation, improvement, conversion, fitting-out, and maintenance work is generally 10%. However, for energy efficiency improvement work, this rate is reduced to 5.5%.

More details on the France Rénov’ website .

Certain regions, departments, intermunicipal authorities, or municipalities may grant additional assistance to national assistance programs for energy efficiency improvement projects.
France Rénov’ advisors can assist individuals with further information.

The energy check is automatically allocated each year, based on household income and composition (people living under the same roof), as declared to the tax authorities.
It can be used to pay electricity or gas bills, purchase fuel oil, wood, LPG, energy renovation work eligible for MaPrimeRénov’ and carried out by RGE professionals, and heating costs indicated in the housing allowance.
No action is required to benefit from the energy check; it is automatically sent to each beneficiary based on the information provided by the tax authorities.

More details about the energy check.

Local authorities may offer an exemption from property tax on certain renovated dwellings.

More details on the France Rénov’ website .

For retirees under the general scheme, the pension fund may grant assistance to carry out work on the home, in particular for:

  • thermal insulation of living spaces,
  • bathroom renovation,
  • boiler replacement,
  • replacement of floor coverings,
  • motorization of roller shutters,
  • housing accessibility.

The property may be occupied as a primary or secondary residence.

From January 1, 2019, until December 31, 2024, future landlords can benefit from tax exemptions when renovating properties in certain medium-sized towns.

Reference text: Decree of March 26, 2016, relating to the list of municipalities eligible for tax reduction.

Landlords who undertake renovation work can deduct the losses incurred by these expenses from their overall income. For energy renovation work, the ceiling for deductible expenses is doubled until December 31, 2025.

Reference text: Decree No. 2023-297 of April 21, 2023, relating to energy renovation work expenses entitling the owner to a temporary increase in the amount of the property deficit that can be deducted from their total income.

For more information:
https://www.economie.gouv.fr/particuliers/tout-savoir-deficit-foncier
https://www.service-public.fr/particuliers/vosdroits/F1991

The zero-interest eco-loan (éco-PTZ) is a loan with no interest and no income requirements, designed to finance energy efficiency improvements.

More information on zero-interest eco-loans and their terms and conditions: financial assistance guides for 2024 (ANAH)

The "renovation advance" mortgage loan has been available to households since 2022 to enable them to finance energy renovation work, partly funded by a public fund. The loan is repaid when the property is sold or upon inheritance. Interest can be repaid periodically or paid when the property is sold or upon inheritance. More and more banks are offering this type of loan, so you should contact them to find out if you are eligible.

Reference text: Articles L312-7 of the CCH and Articles R312-7-1 to 7-5 of the CCH.

  • The Sustainable Development Savings Account loan covers the same work as MaPrimeRénov’ as well as installation costs.
  • Social home ownership loans: eligibility depends on your income and where you live.
  • Loans from energy distributors.
  • Home improvement loan (if you receive benefits from the Family Allowance Fund).

For more information: renovation assistance (ADEME)

To qualify for MaPrimeRénov’ energy renovation grants, certain technical specifications and minimum performance criteria must be met, which may differ from general thermal regulations. We recommend consulting a France Rénov’ advisor to check whether your renovation project is eligible.

Minimum specifications and performanceMetropolitan Franceoverseas territories
Facade or gable wallsR ≥ 3.7m²·K/WR ≥ 0.5m²·K/W
Flat roofsR ≥ 4.5m²·K/WR ≥ 1.5m2.K/W
Roof crawl spaces, attic ceilingsR ≥ 6m2.K/W
R ≥ 1.5m2.K/W
Low floor on basement, crawl space, or open passagewayR ≥ 3m2.K/W
Attic floorR ≥ 7m2.K/WR ≥ 1.5m2.K/W
Table 7: Thermal performance levels (R) to be met in order to qualify for MaPrimeRénov’ financial assistance for thermal insulation work on residential buildings in France.
Minimum specifications and performanceMetropolitan France
Attic floorR ≥ 7m2.K/W
Roof crawlersR ≥ 6m2.K/W
Flat roofR ≥ 6.5m²·K/W
Interior walls (ITI)R ≥ 3.7m²·K/W
Exterior walls (ETICS)R ≥ 4.4m²·K/W
Low floorsR ≥ 3m2.K/W
Table 8: Thermal performance levels (R) to be met in order to qualify for MaPrimeRénov’ Parcours Accompagné financial assistance for thermal insulation work on residential properties in France.

The regulations are also different when it comes to receiving assistance from energy suppliers (CEE scheme) for insulation work.

For residential buildingsMetropolitan FranceOverseas departments and territories1
Insulation of unused attic space R ≥ 7m2.K/WR ≥ 1.5m2.K/W
Insulation of roof slopes R ≥ 6m2.K/WR ≥ 1.5m2.K/W
Wall insulationR ≥ 3.7m²·K/WR ≥ 0.5m²·K/W
Floor insulationR ≥ 3m2.K/W
Table 9: Thermal performance levels (R) that must be met in order to qualify for financial assistance from energy suppliers (CEE) for thermal insulation work on residential buildings in France.
For the service sectorMetropolitan FranceOverseas departments and territories2
Insulation of unused attic space R ≥ 6m2.K/WR ≥ 1.2m2.K/W
Insulation of roof slopes R ≥ 6m2.K/WR ≥ 1.2m2.K/W
Wall insulationR ≥ 3.7m²·K/WR ≥ 1.2m2.K/W
Floor insulationR ≥ 3m2.K/W
Table 10: Thermal performance levels (R) to be met in order to qualify for financial assistance from energy suppliers (CEE) for thermal insulation work on commercial buildings in France.
For industryOverseas departments and territories3
Insulation of unused attic space R ≥ 1.2m2.K/W
Insulation of roof slopes R ≥ 1.2m2.K/W
Wall insulationR ≥ 1.2m2.K/W
Floor insulation
Table 11: Thermal performance levels (R) to be met in order to qualify for financial assistance from energy suppliers (CEE) for thermal insulation work in industry in France.

All information on standardized energy saving measures.

Please visit the ADEME website for detailed information on the regulations governing reduced VAT rates and zero-interest eco-loans, which may vary.

For more details on thermal regulations in the context of renovating existing buildings, consult the documents published by ADEME and the guides available on official websites such as those of the French government orthe National Housing Agency (ANAH).

Insulation work in unused attic spaces is governed by DTU 45.10 (panel or roll insulation) and DTU 45.11 (loose-fill insulation). These French standards set out all the steps that must be followed to ensure compliant and durable installation, beyond the thermal performance requirements.

Check out our comprehensive guide to blowing loose-fill insulation into unused attic spaces.

This comprehensive guide to regulations governing thermal insulation work provides a clear and detailed overview of the legal requirements for improving the energy efficiency of older buildings. Thermal insulation work may sometimes be mandatory during major renovations. In addition to thermal regulations, certain financial assistance programs require higher levels of thermal performance, as is the case for insulation. Finally, last May, ADEME published its recommendations for efficient housing renovation. These recommendations may supplement the regulations on thermal renovation.

  1. Existing or new residential buildings in overseas France, with the exception of new buildings in Réunion constructed at an altitude above 600 m . ↩︎
  2. Existing or new residential buildings in overseas France, with the exception of new buildings in Réunion constructed at an altitude above 600 m . ↩︎
  3. Existing or new residential buildings in overseas France, with the exception of new buildings in Réunion constructed at an altitude above 600 m . ↩︎

Read also...

Get the latest news from Igloo.

On the first Tuesday of every month, receive Igloo News with exclusive content for insulation professionals.

Request an appointment.

Are you a professional and would like more information about cellulose insulation France cellulose insulation ?

Find an applicator.

Would you like to be put in touch with an Igloo France certified professional in your area?